EtherNet/IP to PROFINET Controller Gateway
inkl. mva.
PLX82-EIP-PNC provides EtherNet/IP-based controllers the ability to control up to 36 PROFINET RT devices such as field I/O, drives, HMIs, and controllers.
The EtherNet/IP™ to PROFINET Controller Gateway allows you to connect two giants of industrial automation through secure, high-speed communications. The gateway provides EtherNet/IP-based controllers the ability to control up to 36 PROFINET RT devices such as field I/O, drives, HMIs, and controllers.
The PLX82-EIP-PNC gateways are stand-alone DIN-rail mounted units that provide two Ethernet ports for communications, remote configuration, and diagnostics. The onboard SD Card slot (SD card optional) is used for storing configuration files that can be used for recovery, transferring the configuration to another gateway, or general configuration backup.
Features and Benefits
- Multiple I/O connections allow for high-speed control for large PROFINET I/O systems
- Isolated Ethernet ports allow devices on different protocols to be on different subnets or on the same subnet (must use different IP addresse in same subnet).
- ODVA-approved
- PROFINET v2 certification with PROFINET class A compliance
- Field-tested with multiple PROFINET devices from multiple vendors
- Remotely view and diagnose EtherNet/IP and PROFINET networks
- Embedded EDS AOP provided to allow for seamless integration to Studio 5000 and RSLogix™ 5000
- Using EtherNet/IP I/O connections, no ladder programming is required
Specifications
EtherNet/IP® Specifications
Specification |
Description |
Class 3 Server Connections |
5 |
Supported PLC Types |
PLC2, PLC5, SLC, CLX, CMPLX |
Class 3 Client Connections |
Connected: 2 |
Class 1 I/O Connections |
8 |
Max I/O connection size In/Out |
248/248 |
Min RPI time |
2 ms (1 connection) 8 ms (8 connections) |
CIP Services Supported |
0x4C - CIP Data Table Read 0x4D - CIP Data Table Write |
Command List |
Support for 100 commands per Client, each configurable for command type, IP address, register to/from addressing and word/bit count. |
PROFINET Specifications
Specification |
Description |
Driver Type |
Class 1 RTC, Class 1 RTA |
PROFINET I/O Data |
3840 bytes IN, 3840 bytes OUT |
Exchange Types |
Cyclic Real-time (RT) and Acyclic Data |
PROFINET Devices |
Max: 36 | Max data per device: 1440 bytes in/out |
Hardware
Specification |
Description |
Power Supply |
24 VDC nominal |
Current Load |
24 VDC nominal @ 400mA 10 to 36 VDC @ 610mA maximum |
Operating Temperature |
0° to 50°C (32° to 122°F ) |
Storage Temperature |
-10° to 70°C (-14° to 158°F ) |
Relative Humidity |
5% to 95% RH with no condensation |
Shock |
Operational: IEC 60068-2-27; 15G @ 11ms, 3-Axis Non-Operational: IEC 60068-2-27; 30G @ 18ms, 3-Axis |
Vibration |
IEC 60068-2-6; 5G @ 10 to 150 Hz |
Dimensions |
5.52 x 2.06 x 4.37 in |
Ethernet Port |
10/100Mbit RJ45 Connector Electrical Isolation 1500 Vrms at 50 to 60 Hz for 60 seconds. |
Shipped With Each Unit |
2.5 mm screwdriver, J180 Power Connector |
For mer informasjon og nedlastning av programvare: