IEC 61850 Client Communication Module
incl. VAT
IEC 61850 Client Communication Module for ControlLogix
The ProSoft Technology® IEC 61850 communication module allows Rockwell Automation® ControlLogix® PACs to interface with IEC 61850 Intelligent Electronic Devices (IED) such as substation power monitors and protective relays. The module operates as an IEC 61850 Client supporting the polling of devices using MMS messaging and reports. Additionally, support for GOOSE messaging as both a publisher and subscriber allows for fast data transfer between devices on an IEC 61850 network.
The dual Ethernet ports on the module provide support for Parallel Redundancy Protocol (PRP), and the module supports IEEE C37.238-2017 Power Profile for precision time synchronization of field devices.
https://www.prosoft-technology.com/Products/Rockwell-Automation-In-chassis/Platform/ControlLogix/IEC-61850-Client-Communication-Module-for-ControlLogix
Features and Benefits
- Support for up to 40 IEC 61850 Server devices on the network.
- Support for MMS, MMS Reports, GOOSE publisher, GOOSE subscriber, and control functions on an IEC 61850 Network.
- Parallel Redundancy Protocol (PRP) supported for Ethernet redundancy with compatible devices.
- Time synchronization based on Precision Time Protocol (PTP) support per C37.238-2017 standard (ordinary and boundary clock mode supported).
- The supplied configuration software enables you to import all of your relevant IED tags into your Logix® controller tag database, reducing configuration time and errors.
- Up to 225 I/O connections to the ControlLogix® processor providing large amounts of data to transfer in a real-time environment.
- Standards-based identification of device types simplifies implementation and maintenance.
Configuration
Configuration is accomplished through a custom Add-On Profile for Studio 5000™ that launches the MVI56E-61850C Configuration Manager software, which can be downloaded from www.prosoft-technology.com. The configuration utility automatically creates data tags and Add-On Instruction to be used in ControlLogix® 1756-L8x processors with Studio 5000 version 32 and greater and brings the data over as configured using the tag name of the device in the IEC 61850 network. This intuitive configuration utility saves the user valuable time and effort when building Rockwell Automation® projects with IEC 61850 devices on the network.
Specifications - IEC 61850
Specification |
Value |
Supported Standard |
IEC 61850 Ed 2.0 |
Maximum Number of IEDs |
40 |
Supported Reports |
Buffered Report Control Block (BRCB) |
Control |
Direct-with-Normal-Security |
Maximum Number of Reports per IED |
10 |
GOOSE |
GOOSE Subscription |
Maximum Number of GOOSE |
4 |
Maximum Number of GOOSE |
8 |
Maximum Number of Tags per IED |
500 |
Maximum Number of Tags |
20,000 |
Status |
Status available per node |
Backplane Specifications
Specification |
Value |
Maximum Number of Class 1 Connections |
225 |
Maximum Number of Class 1 High Priority Connections |
50 |
High Priority Connection RPI Range |
[4..9,999] ms |
Normal Priority Connection RPI Range |
[100..9,999] ms |
Maximum Class 1 Connection Input Size |
500 bytes |
Maximum Class 1 Connection Output Size |
496 bytes |
Time Synchronization Specifications
Specification |
Value |
Time Synchronization Standard |
C37.238-2017 |
Supported Modes |
Ordinary Clock, Boundary Clock |
Hardware
Specification |
Description |
Backplane Current Load |
1.4 A @ 5.1 VDC |
Operating Temperature |
-25 to 60⁰C (Series C Chassis) |
Temperature, non-operating |
-40°C to 85°C (-40°F to 185°F) |
Relative Humidity |
5…95% noncondensing |
Vibration |
2g @ 10…500 Hz |
Shock, operating |
30g |
Shock, non-operating |
30g |
Emissions |
IEC 61000-6-4 |
ESD immunity |
4 kV contact discharges |
Radiated RF immunity |
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz |
EFT/B immunity |
+/- 2 kV at 5 kHz on Ethernet ports |
Surge transient immunity |
+/- 2 kV line-earth (CM) on Ethernet ports |
Conducted RF immunity |
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz |
Ethernet Ports (E1, E2) |
(2) GbE RJ45 Connector Link and Activity LED indicators |
Dimensions |
Standard 1756 Single-slot module |